TRI-RATED SINGLE CORE
Buy items
Items TRI-RATED SINGLE CORE
|
Item description
Part no.
|
AWG (approx.) | Outer Ø mm (approx.) | Weight kg/km (approx.) | Metres per Packaging Unit |
|---|
Technical Data
| PVC Single core acc. to UL-Std. 758 (AWM), CSA-Std. C22.2 No. 210 - AWM I A/B, H05V2-K / H07V2-K acc. to EN 50525-2-31, 07V-K in alignment to EN 50525-2-31 | |
| Temperature range | flexible +5°C to +90°C fixed -30°C to +90°C BS (6231) -30°C to +90°C or +105°C / 15.000 hours UL (AWM) -30°C to +105°C |
| Short circuit temperature at the conductor | +160°C (short circuit temperature max. 5 s) |
| Conductor resistance at 20°C | at AWG 22: max. 55,4 Ohm/km |
| Nominal voltage | AC U0/U 300/500 V (EN) ≤1 mm2 AC U0/U 450/750 V (EN) ≥1.5 mm2 UL (AWM) 600 V BS (6231) 600/1000 V |
| Test voltage | 2000 V |
| Minimum bending radius | fixed 6x Outer-ø |
Details
Cable Structure
-
- Copper wire bare, finely stranded acc. to EN 60228 Class 5
-
- Core insulation: PVC acc. to EN 50363-3 (compound type TI3)
-
- Core identification: see datasheet
Properties
-
- the materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
Notes
-
- the conductor is metrically (mm²) constructed, AWG numbers are approximated, and are for reference only
-
- core colours yellow and green, cross-section 1,5 mm² to 16 mm² type 07V2-K in alignment to EN 50525-2-31
Tests
-
- flame-retardant acc. to EN 60332-1-2 / IEC 60332-1-2, UL VW-1, CSA FT1
-
- CPR-class: Eca
Application
-
- Cable suitable for fixed and protected installation, for internal wiring, command and control switchgear and for assemblies of lighting. Cross-sections up to 1 mm2 are only recommended for signal and control circuits. The multiple-standard design makes them adequate to be commercialised worldwide without technical barriers.